Current transformers are clamped around the conductor and measure the consumption of individual equipment and areas without touching the wiring.

Milesight CT101 / CT103 / CT105, smart current transformer
Milesight

CT101 / CT103 / CT105

Smart current transformer

Split-core transformer for retrofitting on equipment, sub-distribution boards and machines. Powers itself from the measured current.

Measured variable
RMS current, 50–60 Hz
Measuring range
CT101 up to 100 A, CT103 up to 250 A, CT105 up to 500 A
Accuracy
±1 % (above 5 A)
Power supply
from the measured current (inductive), optional USB-C
Battery life
not applicable, powered by the measured current
Additionally
Temperature probe (−20 to +100 °C)
Protection rating
IP30
Operating temperature
−20 to +70 °C
Technical datasheet (PDF)
Milesight CT303 / CT305 / CT310, three-phase current transformer
Milesight

CT303 / CT305 / CT310

Three-phase current transformer

Three split-core transformers on one transmitter monitor all three phases of a sub-distribution board or machine separately, without touching the wiring.

Measured variable
RMS current per phase, 50–60 Hz
Measuring range per transformer
CT303 up to 300 A, CT305 up to 500 A, CT310 up to 1,000 A
Accuracy
±1 %
Power supply
from the measured current (inductive), optional USB-C
Battery life
not applicable, powered by the measured current
Additionally
Temperature probe (−20 to +100 °C)
Alerts
Threshold and over-range alarm
Protection rating
IP30
Technical datasheet (PDF)
Dragino CS01-LB, four-channel current sensor converter
Dragino

CS01-LB

Four-channel current sensor converter

Up to four split-core transformers on one device, for running times and consumption of individual machines.

Channels
up to 4 current transformers
Current transformers
100 A, 300 A or 600 A (separate)
Features
Running time, consumption trend, current alarm
Power supply
Battery, 8,500 mAh (Li-SOCl₂)
Battery life
up to around 4 years (manufacturer's calculation, depending on number of transformers and transmission interval)
Operating temperature
−40 to +85 °C
Technical datasheet (PDF)

Technical data according to the manufacturer's datasheet, battery life under the stated conditions. All devices shown transmit via LoRaWAN. In addition to these examples, we also use LoRaWAN devices from other manufacturers depending on requirements.