SECURUS/Hardware/Gateways

LoRaWAN gateways for buildings and equipment

A LoRaWAN gateway receives messages from multiple sensors and forwards them through suitable internet connectivity. Housing, mounting and connections differ for indoor and outdoor locations. We plan gateways and coverage around your measurement points.

Milesight UG63, mini gateway
Milesight

UG63

Mini gateway

Compact gateway for smaller buildings or as a supplement where the radio network still has gaps.

Channels
8
Connectivity
Ethernet, Wi-Fi, optional 4G
Power supply
USB-C (5 V/2 A), 5–12 V DC or PoE via splitter
Battery life
not applicable, mains powered (gateway)
Protection rating
IP30
Operating temperature
−20 to +50 °C
Dimensions
Ø 115 × 21 mm
Mounting
Desk, wall or ceiling
Technical datasheet (PDF)
Milesight UG65, indoor gateway
Milesight

UG65

Indoor gateway

The standard gateway for buildings, in a robust housing also suitable for sheltered outdoor areas.

Channels
8
Connectivity
Ethernet, Wi-Fi, optional 4G
Range
up to 15 km with line of sight, approx. 2 km in built-up areas
Power supply
PoE (802.3af), 9–24 V DC or USB-C
Battery life
not applicable, mains powered (gateway)
Protection rating
IP65
Operating temperature
−40 to +70 °C
Dimensions
180 × 110 × 55.5 mm
Technical datasheet (PDF)
Milesight UG56, industrial gateway
Milesight

UG56

Industrial gateway

Compact gateway in a metal housing for plant rooms and control cabinets, also on a DIN rail.

Channels
8
Connectivity
Ethernet, Wi-Fi, optional 4G
Range
up to 15 km with line of sight, approx. 2 km in built-up areas
Power supply
PoE (802.3af) or USB-C (5 V/2 A)
Battery life
not applicable, mains powered (gateway)
Protection rating
IP30
Operating temperature
−20 to +60 °C
Mounting
Desk, wall or DIN rail
Technical datasheet (PDF)
Milesight UG67, outdoor gateway
Milesight

UG67

Outdoor gateway

For large sites and properties, for mounting on a pole or facade.

Channels
8
Connectivity
Ethernet, optional 4G, GPS
Power supply
PoE (802.3af) or 6–12 V DC
Battery life
not applicable, mains powered (gateway)
Protection rating
IP67
Operating temperature
−40 to +70 °C
Dimensions
240 × 164 × 90.9 mm
Mounting
Wall or pole
Technical datasheet (PDF)
Dragino LPS8N, indoor gateway
Dragino

LPS8N

Indoor gateway

Compact gateway for indoor use, optionally with PoE (LPS8NP) or 4G.

Demodulation paths
10
Connectivity
Ethernet, Wi-Fi, optional 4G
Power supply
USB-C (5 V/2 A), PoE with LPS8NP
Battery life
not applicable, mains powered (gateway)
Dimensions
120 × 120 × 30 mm
Technical datasheet (PDF)

Technical data according to the manufacturer's datasheet, battery life under the stated conditions. All devices shown transmit via LoRaWAN. In addition to these examples, we also use LoRaWAN devices from other manufacturers depending on requirements.

Plan gateway placement and radio coverage

Building materials, metal and installation location affect reception. Check connectivity at the intended sensor positions. Power and internet access are planned too. The fundamentals section below explains how sensors, gateways and platform work together.

In practice

Understand LoRaWAN: from sensor to platform

A gateway is part of the full data path. These fundamentals support selection and planning.

What does LoRaWAN mean?

LoRaWAN means Long Range Wide Area Network. LoRa is the underlying radio technology; LoRaWAN defines the communication protocol and network architecture. Put simply, a device measures a value and sends a small message. A gateway within range receives it and forwards it to the network infrastructure.

The technology is designed for low-power transmission of small data messages. It suits many sensing tasks, rather than video streams or large file transfers. Safety-related machine control with guaranteed response times is also a different task from building monitoring.

Sensors, gateways and platforms: who does what?

A LoRaWAN sensor measures temperature, humidity or a switching state, for example. It does not need Wi-Fi. A LoRaWAN gateway receives radio messages from multiple devices and connects the radio network to the wider infrastructure. The gateway needs power and a suitable connection, such as Ethernet or cellular, depending on the model.

A network server handles LoRaWAN communication. The application then makes the payload useful by assigning readings to rooms, showing histories and generating alerts. A gateway alone is therefore not a complete monitoring solution. Sensor integration, data processing and operational responsibilities are also needed.

What range does LoRaWAN achieve indoors?

One blanket range figure is of limited use for a particular building. Concrete, metal, shafts, cold rooms and antenna placement affect reception. A gateway inside a shielded control cabinet faces different conditions from a suitably located receiver higher in the building.

Plan coverage around the actual measurement points. Testing at the intended installation point is more informative than a distance on a floor plan. Gateway position or number can be adjusted if needed. Device failures and interrupted connections must also be identifiable during operation.

How long does a LoRaWAN sensor battery last?

Many sensors run on batteries. Battery life depends on measurement method, transmission interval, radio conditions, temperature and battery type. Frequent transmissions use more energy than occasional status messages. A datasheet lifetime therefore applies only under its stated conditions.

Measurement intervals are a deliberate choice. Slowly changing room climate readings may need a different interval from a water alarm. Device selection must check whether an event is transmitted immediately or only as part of a periodic message.

FAQ

Frequently asked questions about LoRaWAN

Does each sensor need its own gateway?

No. Many LoRaWAN sensors can share one gateway. Depending on the building, one well-positioned gateway may be enough; multiple floors, shielding or separate sites may require additional gateways. We check coverage at the planned monitoring points.

How many sensors can a LoRaWAN gateway support?

Milesight specifies more than 2,000 devices for models such as the UG65 and UG67. This manufacturer figure is not a universal capacity guarantee for every project. Relevant factors include transmission frequency, message size, radio conditions and the number of devices transmitting at the same time. We account for these when planning the network.

How does the gateway connect to the internet?

Depending on the model and configuration, it connects via LAN/Ethernet, Wi-Fi or 4G/LTE with a SIM card. Cellular access requires a compatible gateway variant, a data plan and reception at the installation point. The sensors themselves need neither Wi-Fi nor a SIM card: they send data to the gateway via LoRaWAN.

What range does LoRaWAN offer?

For the UG65, Milesight quotes around 2 km in built-up areas and up to 15 km with a clear line of sight. These manufacturer figures are guidance, not a guarantee for a building. Concrete, metal, cold rooms, antenna placement and interference can substantially affect reception. We therefore check the radio connection on site.

Are all LoRaWAN sensors battery-powered?

No. Many temperature, humidity and leak sensors run on batteries. Other devices need a continuous power supply, for example via USB-C. Examples include air-quality sensors with energy-intensive sensing methods, such as the AM319. The sensing method and operating mode matter, not just the amount of data transmitted.

How long do sensor batteries last?

Low-power sensor types can achieve five to ten years. This depends on the model, battery, measurement and transmission intervals, radio conditions and ambient temperature. For example, Milesight quotes around 5.8 to over ten years for the EM300-TH at a ten-minute reporting interval and 25°C in the EU868 band, depending on radio settings. These are laboratory figures for guidance. A twenty-minute interval alone does not guarantee a particular battery life.

Does a sensor only send an alarm every twenty minutes?

Not necessarily. Regular reporting and event-triggered messages are different functions. Suitable devices can, for example, report water detection in addition to their normal reporting interval. Availability and behavior depend on the sensor and configuration. During commissioning, we test the path from the event to the notification.

Which gateway suits your building?

We select the right device with you, integrate it into SECURUS and deliver it ready for use.